Count conductors, grounds, clamps and devices against your box volume using Section 314.16 allowances.
How it works
Each conductor counts once at its Table 314.16(B) volume. All internal clamps count once together. Each device yoke counts twice, grounds count once for the first four and a quarter each after that, and a fixture stud counts once.
Before you order
- Use the volume stamped inside the box, or the listed volume for plastic boxes.
- Twist-on connectors and short pigtails do not add allowance.
- GFCI receptacles are bulky even though they count the same, so go a size up.
Common questions
Why does a device count as two wires?
Code gives each yoke a double allowance based on the largest wire connected to it.
Do all grounds count as one?
Under the 2020 and later rule, up to four count as one and each additional ground counts as a quarter. Older editions and some local rules count differently.