Voltage Drop Calculator

How much voltage will I lose on this wire run?

Circuit
Conductor
Wire size
A
ft

Your voltage drop is

7.9volts dropped

6.6% of 120 V. Above the code-recommended 3% for a branch circuit. Planning figure only. Confirm against the electrical code your area has adopted and have a licensed electrician check the work.

SourceLoad120 V112.1 V at load100 ft one wayDrop: 7.9 V (6.6%)
Percent drop6.58%
Voltage at load112.1 V
Circular mils6,530
Formula2 × 12.9 × I × L ÷ CM

Long runs waste voltage, and motors and lights suffer for it. Enter the wire, load and distance to see the drop in volts and percent.

How it works

Uses 2 × K × amps × one-way length ÷ circular mils for single phase and 1.732 in place of 2 for three phase. K is 12.9 for copper and 21.2 for aluminum, with circular mils from the electrical code Chapter 9 Table 8.

Before you order

  • Use one-way distance. The formula already counts the return path.
  • Code guidance suggests about 3% on a branch circuit and 5% total including the feeder.
  • If the drop is high, step up one wire size and check that it still fits the conduit.

Common questions

Is 3% voltage drop a code requirement?

In most editions it is an informational recommendation, not a rule. Local amendments and equipment makers can be stricter, so check before relying on it.

Does this account for power factor?

No. The simplified K method works well for short residential runs. Long feeders and motor loads need a calculation that includes reactance.