Check THHN wires in EMT against the percentage limits in the electrical code Chapter 9.
How it works
Adds the Table 5 area of every wire, divides by the Table 4 inside area of the conduit, and compares to the Table 1 limit: 53% for one wire, 31% for two, 40% for three or more.
Before you order
- Count every conductor, including neutrals and grounds, because they all take up room.
- Pulling is easier well under the limit, especially on runs with several bends.
- Bundling many current-carrying wires can reduce their ampacity even when the fill passes.
Common questions
Why are 4 and 3 AWG missing?
We only list wire sizes where we could confirm the published area, so those two and any conduit over 1-1/2 in are left out for now.
Can I use this for PVC?
Not as written. PVC has a smaller inside area than EMT of the same trade size, so use the PVC column in Table 4.